PF4 – Differential-Pressure Transmitter

Liên hệ

Applications
The ROTRONIC differential-pressure transmitters are ideal for clean rooms, operating rooms and applications where even minor differences in pressure can have a big effect.

Features 
• High-precision measurement and long-term stability 
• Fast response time and low hysteresis 
• Analog signals freely configurable 
• Integrated relay switch contact 
• Large overload range 
• Expandable with HygroClip2 sensor or analogue inputs
• High immunity to dust and humidity in the medium

Dimensions129 x 72 x 45 mm
Weight240 g
Range of application0…70 °C / 0…90 %rh; 0…60 °C / 0…90 %rh with display
Accuracy at 23 ±5 °C±1.0 % of full scale @ 23 °C ±3 K
InputsDifferential pressure, hose connections, 4 mm internal diameter Optional: HygroClip2 / analog input 1 Pt100 connection, 4-wire
Measuring range-25…+25 Pa / -50…+50 Pa -100…+100 Pa / -250…+250 Pa -500…+500 Pa -100…200 °C (probe-dependent) 0…100 %RH (with HC2)
Pressure dependency0.1 %/hPa
Pressure resistance2 bar (2’000 hPa)
Air flow120 – 180 μl/min
Accuracy analog output±10 mV (voltage output); ±20 μA (current output)
Switch output1 relay, Time delay, duty cycle, resetting configurable
Switching capacity<50 VAC / <75 VDC / <1 A
Power supply15…40 VDC / 14…28 VAC
Current consumption<70 mA / <150 mA (with Ethernet)
Long-term stability sensor<0.3 %/ year
Response time t 63<10 ms (only sensor element)
Alarm functionsConfigurable relay, HW4
Type of output signalsVoltage, current, digital (optional)
Analog output signal (standard)0…1 V, 0…5 V, 0…10 V, 0(4)…20 mA
Communication interfacesEthernet (optional)
HousingABS
Cable connections1 x M16, terminal
IP protection ratingIP65
FDA / GAMPFDA 21 CFR part 11 / GAMP5
Temperature adjustmentSingle-point
CE / EMC conform2004/108/EC
Nhà cung cấp

Chưa cập nhật

Xuất xứ

Chưa cập nhật

Đánh giá

Chưa có đánh giá nào.

Hãy là người đầu tiên nhận xét “PF4 – Differential-Pressure Transmitter”